VOPV1000-3/3 combines 3 photovoltaic input circuits into 3 protected outputs. The wall-mounted assembly integrates string fuses, Type 2 DC surge protection and VOD1 load-break isolation in an IP65 enclosure.
02 / TECHNICAL DATA
VOPV1000-3/3 technical data
Use these values for initial selection. Confirm string voltage, corrected current, fuse coordination, internal circuit arrangement and controlled documentation before ordering.
Electrical, protection and enclosure specifications
Maximum system voltage1000 V DC
Input / output arrangement3/3
Maximum output current45 A
Protection degreeIP65
Enclosure modelVOAT-39
Enclosure dimensions (W × H × D)296 × 550 × 130 mm
Enclosure materialPC / ABS
Impact resistanceIK10
String fuse holders6 × VOPV-32
Fuse links6 × 10 × 38 mm, 15 A
DC surge arresters3 × Type 2, 40 kA
PV switch disconnectors3 × VOD1-63
Cable entry range2.5–16 mm²
Operating temperature-20°C to +60°C
InstallationWall mounting
Maximum altitude≤2000 m
HumidityUp to 99%
Enclosure dimensions
Dimension drawing
Request the current dimension drawing for this model.
03 / PRODUCT SELECTION
Configure VOPV1000-3/3
04 / APPLICATIONS
Applications for VOPV1000-3/3
01
PV string protection
Protect 3 photovoltaic input circuits with dedicated positive and negative fuse links.
02
Surge protection and isolation
Integrate Type 2 DC surge protection and load-break isolation ahead of the inverter or DC distribution equipment.
03
Outdoor wall mounting
Use the IP65 PC/ABS enclosure for protected wall-mounted photovoltaic installations.
05 / RESOURCES
VOPV1000-3/3 controlled documents
Request documents matched to the final circuit arrangement and destination market.
What is the circuit arrangement of VOPV1000-3/3?
VOPV1000-3/3 has 3 photovoltaic inputs and 3 protected outputs.
What is the maximum voltage of VOPV1000-3/3?
The listed maximum system voltage is 1000 V DC. Confirm the corrected cold-weather array open-circuit voltage before selection.
Which protection devices are included?
The listed bill of materials includes 6 VOPV-32 fuse holders with 15A fuse links, 3 Type 2 DC surge arresters and 3 VOD1-63 switch disconnectors.
Can the internal components be changed?
Project-specific component and enclosure requirements can be reviewed. The final bill of materials and order code must be confirmed in the quotation.